Properties that can be adjusted using software

  • Free assignment of the functions switching, dimming, blind and encoder to inputs 1 through 4 or pulse counters and switch counters to inputs 1 and 2
  • Blocking object for blocking individual inputs
  • Behaviour when the bus voltage is restored can be parameterized separately for each input
  • Telegram rate limitation
  • Switching function: two independent switching objects are available for each input and can be released individually, command for leading and trailing edge can be set independently (ON, OFF, CHANGE, no reaction), cyclical transmission of the switching object depending on the edge or depending on the object value can be selected
  • Dimming function: single and double-surface operation, time between dimming and switching and dimming increment can be set, telegram repetition and stop-telegram transmission possible
  • Blind function: command can be set with rising edge (no function, UP, DOWN, CHANGE), operating concept can be configured (Step - Move - Step or Move - Step), time between short-term and long-term operation can be set, slat adjustment time can be set
  • Encoder and light scene auxiliary unit function: edge (button as NO contact, button as NC contact, switch) and value with edge can be parameterized, value adjustment with button by pressing and holding button for encoder possible, light scene auxiliary unit with memory function and saving of the scene without previously calling up is possible
  • Encoder for temperature and brightness function: edge and value configurable, value adjustment with button is possible by pressing and holding button
  • Pulse counter function: edge for pulse counting and interval time for counter status transfer can be parameterized, edge of the synchronisation signal for resetting the counter status and switching telegram when synchronisation signal arrives can be set
  • Function of switching counter: edge for counting the signals at the input and max. counter status are selectable, step size for counter status output and telegram when the max. counter status is reached can be parameterized

Technical data

Number of inputs

2 or 4

Connections

KNX via connection and junction terminal 0595 00

Input cable

via 3-wire or 5-wire cable set

Temperature range

-5ºC to +45ºC

Protection type

IP 20

Dimensions

L x W x H 43 x 28 x 15 mm