Gira KNX switching actuators, 1-gang 16 A, 2-gang 6 A

Gira KNX switching actuator, 1-gang, 16 A

The Gira KNX 1-gang 16 A and 2-gang 6 A switching actuators, are equipped with two binary inputs for installation in a flush-mounted switch box (the electronics box from Kaiser is recommended). Potential-free contacts can be connected to them. The two inputs can carry out various functions or be blocked independently of each other. As a factory setting, the input 'One' (1-gang variant 16 A) and the two inputs of the 2-gang variant 6 A are assigned to the outputs of the switching actuator so that operation is possible without programming. 

The connection to 230 V is via a flexible cable approx. 20 cm in length. The binary inputs and the KNX are connected via a 6-wire connection cable approx. 30 cm in length. The connection cable for the binary inputs can be extended to a maximum of five metres.

Output/outputs

  • Output can be parameterized as NO contact or NC contact 
  • Selection of preferred position in the event of bus power failure and recovery
  • Switch-on and/or switch-off delay or time-switch function can be set 
  • Output with three objects: switching, feedback, and additional function (linking, blocking function or forced setting) 
  • Feedback object can be inverted

Inputs

  • Free assignment of the switching, dimming, blind and encoder functions to both inputs
  • Blocking object for blocking individual inputs
  • Behaviour when the bus voltage is restored can be parameterized separately for each input
  • Telegram rate limitation
  • Switching function: two independent switching objects are available for each existing input and can be enabled individually, command for leading and trailing edge can be set independently (ON, OFF, CHANGE, no reaction)
  • Dimming function: single and double-surface operation, time between dimming and switching and dimming increment can be set, telegram repetition and stop-telegram transmission possible
  • Blind function: command can be set with rising edge (no function, UP, DOWN, CHANGE), operating concept can be parameterized (Step - Move - Step or Move - Step), time between short and long-term operation can be set, slat adjustment time can be set
  • Encoder and light scene auxiliary unit function: edge (button as NO contact, button as NC contact, switch) and value with edge can be parameterized, value adjustment with button by pressing and holding button for encoder possible, light scene extension with memory function and saving of the scene without previously calling up is possible

Technical data for the 1-gang variant 16 A

Switching contact

Relay with 1 x potential-free NO contact

Load capacity

AC 230 V / 16 A

Connected load

2500 W light bulbs
2200 W HV halogen
1000 VA LV halogen
wound transformer,
1000W LV halogen
Gira Tronic transformer
10 A, max. 105 µF capacitive load

Number of inputs

2

Temperature range

-5°C to +45°C

Protection type

IP 20

Dimensions

L x W x H 51 x 48 x 28 mm

Installation

electronics box
Kaiser order no. 1068-02
Kaiser order no. 9062-94 (wind-proof)
Kaiser order no. 9062-74 (halogen-free)

VDE approval in accordance with

EN 60669-1, EN 60669-2-1, EN 50428

Technical data for the 2-gang variant 6 A

Switching contact

Relay with 2 x potential-free NO contacts

Load capacity

AC 230 V / 6 A

Connected load

1200 W light bulbs
1200 W HV halogen
500 VA LV halogen
wound transformer,
500W LV halogen
Gira Tronic transformer,
6 A, max. 14 µF capacitive load

Number of inputs

2

Temperature range

-5°C to +45°C

Protection type

IP 20

Dimensions

L x W x H 51 x 48 x 28 mm

Installation

electronics box
Kaiser order no. 1068-02
Kaiser order no. 9062-94
(wind-proof)
Kaiser order no. 9062-74
(halogen-free)

VDE approval in accordance with

EN 60669-1, EN 60669-2-1, EN 50428

The delivery results subject to countries specific assortments

Interfaces