Gira KNX switching actuators with manual actuation and current measurement for C loads

Gira KNX switching actuator, 4-gang 16 A with manual actuation and current measurement for C loads

The Gira KNX switching actuators with manual actuation and current measurement for C loads are available as 4-gang or 8-gang 16 A variants. They are equipped with an integrated bus coupler and used to switch either four or eight independently controllable load groups. The integrated manual switch can be used to trigger relay switchover (On / Off) in parallel or without KNX/EIB operation. The device variants’ switching contacts are specially designed for loads that are capacitive in nature and for resulting brief, high starting currents.

They feature integrated current detection. Separate current measurement can be carried out for each channel. The DRA actuators are installed on a DIN top-hat rail, and no other power supply is necessary. Gira recommends ETS 3.0 d for configuring and starting up the device.

Functions

  • Independent switching of 4 or 8 outputs
  • Manual actuation of the relay independent of the bus or switching position indication
  • NO contact or NC contact operation
  • Central switching function
  • Group feedback for reduction of bus load
  • Active or passive cyclical feedback function (object can be read out)
  • Feedback can be delayed until after the bus voltage is restored
  • Logical linking function for each channel
  • Blocking function can be parameterized for each channel. As an alternative, forced setting function for each output
  • Time functions (switch-on/switch-off delay, staircase light function - also with advance warning function)
  • Inclusion in light scenes possible, maximum of 8 internal scenes can be parameterized per channel
  • Memory function for light scenes
  • Elapsed operating time meter as up/down counter with limit function (limit can be changed via bus) can be activated for each output
  • Input monitoring for cyclical updating with safety setting
  • Reactions in the event of bus voltage failure and recovery can be set for each channel following an ETS programming process
  • Current detection, measurement of load current for each channel
  • Limits for load monitoring (e.g. signalling of load failure)

Technical data

Switching contact

Relay with 4 or 8 potential-free NO contacts

Switching capacity AC 230 V

16 A / AC 1 or 16 A / AC 3

Switching capacity AC 400 V

10 A / AC 1 or 10 A / AC 3

Switching capacity DC

16 A / 24 V

Max. switch-on current

600 A, 150 µs
300 A, 600 µs

Connected load

3680 W Ohmic load
16 A, max. 200 µF
Capacitive load AC 230 V
3680 W light bulbs
3680 W HV halogen
2000 VA LV halogen,
wound transformer
2500 W LV halogen,
Gira Tronic transformer
3680 VA fluorescent lamps,
uncompensated
3680 VA fluorescent lamps
Lead-lag circuit
2500 VA fluorescent lamps
with parallel compensation
3680 W Mercury-vapour lamps uncompensated
3680 W Mercury-vapour lamps with parallel compensation

Current detection

0.25 to 16 A sinus
50/60 Hz

Connections

KNX via connection and junction terminal 0595 00
Load via screw terminals
0.2 to 4 mm² single-wire
2 x 0.2 to 2.5 mm² single-wire
0.75 to 4 mm² fine-wire
without core jacket
0.5 to 2.5 mm² fine-wire
with core jacket

Dimensions

DRA device with 4 or 8 HP

VDE approval in accordance with

EN 60669-1, EN 60669-2-1, EN 50428

The delivery results subject to countries specific assortments

Switching actuators

TOP